H05VV-F (TTR) | |||||||
300 / 500 V | |||||||
Code | : | H05VV-F | |||||
Standarts | : | TS 9760, IEC 227, VDE 0281, BS 6500 |
|
||||
Construction | : | 1- Flexible Copper Conductor | |||||
2- PVC insulation, 3- PVC Filling, 4- PVC Outer Sheat | |||||||
Application | : | For household appliances under medium mechanical stress-also | |||||
in damp and wet areas | |||||||
Technical Data | : | Max. operating temperature 70 ºC | |||||
Short circuit temperature 160 ºC | |||||||
NO. of Cores &Nominla Cross Section | No. of wires &Diameter | Thickness of Insulation | Thickness of Sheath | Approx. Overall Dia | Conductor DC Resistance at 20°C | Max.Current Carrying Capacity at 30°C | |
mm2 | mm | mm | mm | mm | ohms/km | Air A | |
2x0.75 | 22x0.2 | 0.6 | 0.8 | 6.4 | 26 | 8 | |
2x1 | 30x0.2 | 0.6 | 0.8 | 6.6 | 19.5 | 12 | |
2x1.5 | 27x0.25 | 0.7 | 0.8 | 7.4 | 91 | 18 | |
2x2.5 | 45x0.25 | 0.8 | 1 | 9.2 | 7.98 | 26 | |
2x4 | 50x0.3 | 0.8 | 1.1 | 11 | 189 | 32 | |
3x0.75 | 22x0.2 | 0.6 | 0.8 | 6.8 | 26 | 8 | |
3x1 | 30x0.2 | 0.6 | 0.8 | 7 | 19.5 | 12 | |
3x1.5 | 27x0.25 | 0.7 | 0.9 | 8.1 | 109 | 18 | |
3x2.5 | 45x0.25 | 0.8 | 1.1 | 10 | 7.98 | 26 | |
3x4 | 50x0.3 | 0.8 | 1.2 | 11.9 | 4.95 | 32 | |
4x0.75 | 22x0.2 | 0.6 | 0.8 | 7.4 | 26 | 8 | |
4x1 | 30x0.2 | 0.6 | 0.8 | 7.9 | 19.5 | 12 | |
4x1.5 | 27x0.25 | 0.7 | 0.8 | 9 | 13.3 | 18 | |
4x2.5 | 45x0.25 | 0.8 | 1.1 | 10.9 | 7.98 | 26 | |
4x4 | 50x0.3 | 0.8 | 1.2 | 13.2 | 306 | 32 | |
5x0.75 | 22x0.2 | 0.6 | 0.8 | 8.3 | 101 | 8 | |
5x1 | 30x0.2 | 0.6 | 0.9 | 8.6 | 19.5 | 12 | |
5x1.5 | 27x0.25 | 0.7 | 1 | 10.1 | 13.3 | 18 | |
5x2.5 | 45x0.25 | 0.8 | 1.1 | 12.8 | 7.98 | 26 | |
5x4 | 50x0.3 | 0.8 | 1.3 | 14.8 | 4.95 | 32 |